Products
Contact Us
- Contact Person : Ms. zhu Helen
- Company Name : Wuhan Feite Electric Co., Ltd.
- Tel : 86-027-84799945
- Fax : 86-027-84799945
- Address : Hubei,Wuhan,No. 108, Dazhuan Road, Caidian District
- Country/Region : China
- Zip : 430113
AC high voltage vacuum load breaking switch
Product Detailed
Related Categories:Other Switches
1.30 years'exerience
2.export Europe Middle East Southeast Asia Austrilia
3.ODM OEM, CE CB
Main Technical Data | |||||
Type | FZN25-12D/T630-20 | FZN25-12D/T125-31.5 | |||
Rated voltage | kv | 12 | |||
Rated frequency | Hz | 50 | |||
Rated current | A | 630 | 1250 | ||
Rated short-time power frequency withstand voltage(1 min) | kv | Fructure of vacuum interrupter 30 | |||
Rated short-time power frequency withstand voltage (valid) | kv | Interphase or to ground 42,fructure 48 | |||
Rated lighting impulse withstand voltage | kv | Interphase or to ground 75,fructure 85 | |||
Rated dynamic stability current (peak) | kA | 50 | |||
4S thermostability current | kA | 20 | |||
Rated breaking current of active load | A | 630 | |||
Rated breaking current of close loop | A | 630 | |||
Rated breaking current of cable charging current | kA | 10 | |||
Rated capacitor volume of breaking non-load | kv | 1600 | |||
Rated transfor current | v | 2000 | |||
Model od fuse protector | SDLAJ-12 | ||||
Output of energy of collider | 2~5 | ||||
Rated dynamic stability current of earth switch | kA | 50 | |||
2S dynamic stability current of earth switch | kA | 20 | |||
Rated voltage of assist circuit | v | AC,DC220 AC,DC110 | |||
Mechanical life | times | 10000 | |||
Opening time triggered by fuse protector | ms | 30~40 | |||
Opening time triggered by release | ms | 40~50 | |||
Note:Rated characteristics can be given on requirment |